timer auto drain valve function 99 hours


Tonhe A 20-S Series

Timer Controlled shut off Valve

Application

l Water meter , water leak detection system and water treatment etc equipment

l HAV and fire works. Automatic drain system

l Irrigation ect small control equipment

ADDNo.1012 Xincheng Road, Huangyan, Taizhou, Zhejiang, China

EMAIL: tonhe08@china-tonhe.com
Mobile:+86-18957612187

Skype:meizi2661

UL: www.china-tonhe.com



Technical Parameters:

Product size

□NPT/BSP1/4 3/8 1/2"' □NPT/BSP 3/4'' □NPT/BSP 1"
□NPT/BSP 1 1/4'' (Optional )

Maximum working pressure

1.0 MPa

Circulation medium

Fluid, air

Valve open /closed time

7 seconds

Rated voltage

AC/DC9-24V AC110-230V (Optional )

Setting valve open time

Any time in 0-24H

Setting valve closed time

Any time in 0-24H

Working current

500MA

Stall current setting

0-599mA

Life time

100000 times

Valve Body material

Brass □Nickel plated Brass □304 Stainless steel Optional

Actuator material

Engineering Plastics

Sealing material

EPDM & PTFE

Actuator rotation

90°

Max. torque force

4N.M

Cable Length

0.5m,1.5mOptional

Environment temperature

-15℃50℃

Liquid temperature

2℃90℃

Manual override

No

Indicator

Yes

Protection class

IP67

1 Parameter specifies

Working voltage :AC110-230V/AC/DC9-24V

Setting valve open time : any time in 0-24H

Setting valve close time : any time in 0-24H

Valve close automatic in case of power is failure

2 Timer specification

3 Operation instruction

Actuator parameter setting have two menu structures on below:

Function code ( fist menu),

The setting parameters of function code ( secondary menu)

Picture 0 Secondary menu operation menu

Function code

Content

Value

Unit

Remarks

t on

valve  keeping open time

00:00:00 99:59:59

H:M:S


toFF

valve keeping closed time

00:00:00 99:59:59

H:M:S


PonS

Power -on Action

On/oFF



Prot

Stall current setting

0-599

MA

When the current is bigger than the setting value 1.6S, the motor will stop working , and the display will show Err.

Parameter function control table

4 Stalling protection function

When the actuator is detected stalling, it will run in reverse direction .when reach to the open or closed position , and do the close or open action again , meanwell displaying flashed 0000-0001 on screen ( indicating the current retrying times ) . If it fail at third retrying , the valve will stop running and display ERRL on the screen .